Theoretical background

 

 

Several pages in this Help contain technical notes, useful for a better understanding of Advance Design RC Wall module.

 

Find below the list of technical notes, as included in their corresponding topics:

 

 

BEARING WALL EXAMPLE

 

 

 

 

Bearing Wall

 

 

 

 

 

- G = 600kN/ml

- Q = 150kN/ml

 

 

Design axial force at the ULS

 

Because of self-weight, the design force will slightly differ on the top, middle, and bottom of the wall.

 

 

NEd = 1,35 x 600 + 1,5 x 150 = 1035 kN/ml

NEd = 1035 x 8,5 = 8798 kN

 

NEd = 1,35 x (25 x 0,18 x 3/2 + 600) + 1,5 x 150 = 1044 kN/ml

NEd = 1044 x 8,5 = 8874 kN

 

NEd = 1,35 x (25 x 0,18 x 3 + 600) + 1,5 x 150 = 1053 kN/ml

NEd = 1053 x 8,5 = 8951 kN

 

 

 

Compressive strength

 

Compressive strength is given by:

 

 Compressive strength

 

the value of the design

 

 

With:

 

Recommended value

 

 

Materials

 

 

 

Note: French annex also recommends acc,pl =1,0 when 2nd order effects are considered (means when checking the axial in the middle of wall).

 

 

Note

 

 

η

 

 

Therefore, on the top and bottom of the wall (where no 2nd order effects are considered):

 

 

top and bottom of the wall

But in the middle of the wall (where 2nd order effects are considered):

 

in the middle of the wall

 

 

 

Wall slenderness and buckling length

 

Wall slenderness is given by:

Wall slenderness

 

Values

 

 

 

RC Wall Designer results

 

 

Slenderness calculation

 

 

Wall slenderness does not exceed 86, allowing for plain concrete wall.

 

Slenderness of walls

 

 

 

Axial resistance of plain concrete wall

 

The axial resistance of the wall should be further verified:

 

 

 

Top of the wall

 

The axial resistance NRd is given by:

 

The axial resistance

 

 

RC Wall Designer results

 

 

RC Wall Designer results

 

 

 

 

 

Bottom of the wall

 

The axial resistance NRd is given by:

axial resistance

 

 

 

RC Wall Designer results

 

 

Bottom of the wall

 

 

 

 

 

Middle of the wall

 

The axial resistance NRd is given by:

 

Middle of the wall

 

Braced members

 

Note: The French Annex recommends a slightly different formula:

 

 

Note

 

Note: The French Annex introduces an extra condition:

 

French Annex

 

 

Particular rules

 

Vertical reinforcement

 

The minimum and maximum values of the vertical reinforcement are given by:

 

Vertical reinforcement

 

 

 

RC Wall Designer results

 

 

Minimal constructive dispositions

 

 

Horizontal reinforcement

 

The minimum and maximum area of the horizontal reinforcement are given by:

 

Horizontal reinforcement

 

Max spacing between horizontal bars is defined in §9.6.3(2) from EN1992-1-1:

 

(2) The spacing between two adjacent horizontal bars should not be greater than 400 mm.

 

 

RC Wall Designer results

 

 

Minimal horizontal reinforcement

 

 

 

Peripheral ties

 

Requirements regarding peripheral ties are defined in §9.10.2.2 from EN1992-1-1:

 

 

Peripheral ties

 

 

Note: The French Annex uses other values.

 

The French Annex

 

 

RC Wall Designer results

 

 

Horizontal Linkage

 

 

 

 

 

Shear Wall design general description

 

The shear wall design can be summarized by the following sequence:

 

 

 

1.Vertical reinforcement design using composed bending method

 

Using the dimensioning resultant forces (M,N), a first composed bending design is performed and the reinforcement area to be placed on the vertical stiffeners at the extremities of the wall is calculated. The neutral axis position is also calculated.

 

 

Vertical reinforcement design

 

 

 

 

 

 

Calculation details regarding this step can be found in a report in the chapter "Vertical reinforcement-Detailed calculation - for Composed Bending considering edge stiffeners method".

 

2.Stiffeners reinforcement and shear verifications

 

The program further applies the constructive dispositions according to EN 1998-1 (if Seismic dispositions are activated) to calculate :

 

 


3. Neutral axis position optimization considering the real reinforcement in place and the out of plane verification

 

According to article 5.4.3.5.1 (2) P from EN1998-1: « Normal stresses in concrete shall be limited to prevent out-of-plane instability of the wall »

 

To optimize this verification, several iterations over the position of the neutral axis are done. Indeed, after the composed bending design is performed (to calculate the edge stiffeners vertical reinforcement), the theoretical position of the neutral axis is known.


From the actual reinforcement in the wall (reinforcement in edge stiffeners and in the wall web), the module searches for the new real position of the neutral axis: it is an iterative calculation that searches for balance by trying to limit the shortening on the concrete to limit the compression on the end strips.


For each iteration, the calculation is the same:

 

 

The strain diagram

 

 

 

 

the deformation diagram

 

 

 

 

 

Attention: The module also takes into account compressed reinforcement:

 

compressed reinforcement

 

 

 

 

Calculation details regarding this step can be found in the report in the chapter Vertical reinforcement-Out of plane verification.

 

 

4.Shear verification at the interface between concrete cast at different times

 

Finally, the module performs a shear verification at the interface between concrete cast at different times considering the new position of the neutral axis and the real reinforcement in place:

 

Shear verification

 

 

 

Attention, the calculation of the reinforcement percentage, ρ, to take into account is different according to the position of the wall (a choice which is made in the menu Design Assumptions / EC8 Seismic Dispositions):

 

 

 

In the Interface Verification dialog, the user can activate or not the generation of additional interface reinforcement bars (along the wall web) to increase the term Ar for the shear verification at the interface between concrete cast at different times:

 

 

Interface verification

 

 

 

If the user has not checked this option, a message indicates this possibility in info-panel, in case the force applied is greater than the resistant force:

 

 

info panel

 

 

 

Finally, if the user has checked this option, and the term VRdi is exceeded, the module itself increases the reinforcement, but only the vertical reinforcement which crosses the section of recovery, to satisfy the verification of shear at interface between concrete cast at different times.

 

 

SHEAR WALL EXAMPLE

 

 

SHEAR WALL

 

Resulting forces

 

 

 

1.Composed bending design

 

The critical set of resulting forces results from the following combination:

 

1× [G]-1 × [S]-0.3× [S]

 

Composed bending design

 

2.2nd order effects (out-of-plane strip buckling)

 

The critical combination for this verification is:

 

1× [G]-1 × [4S]+0.3× [3S]+0.3× [2Q]

 

In this combination, the wall is entirely compressed (compressed length = wall length = 5.00 m)

 

SECOND ORDER EFFECTS

 

out-of-plane strip buckling

 

 

The compressed length (length = 5 m) is then divided into 11 intervals:

 

The 1st interval (edge stiffener) requires 0 cm² for out of plane verification.

 

This is covered by the 19.63 cm² already in place. This happens for all intervals and thus the real vertical reinforcement does not need to be increased for this verification.

 

 

RC Wall Designer results

 

Final reinforcement values

 

 

Shear verification at the ULS (§6.2 from EN1992-1-1)

 

Design shear resistance at the ULS (6.2 from EN1992-1-1) Verification:

Design shear resistance at the ULS

 

 

Verification is passed.

 

The wall is designed as a plain concrete wall.

 

 

VRd,max calculation (6.2.3)

 

 

 

VRd,max calculation (6.2.3)

 

 

Note: According to 6.2.2(1) from EN1992-1-1, Asl is the tensile reinforcement area. For this combination, the wall is entirely compressed so

 

VRd,c calculation

 

Shear at the interface between concrete cast at different times at the ULS (6.2.5 from EN1992-1-1)

 

 

Shear at the interface between concrete cast at different times at the ULS

 

Shear at the interface between concrete cast at different times at the ULS (6.2.5

 

Note: Asl is given by one edge stiffner (4Ha25 = 19.63 cm²) and the vertical web reinforcement (11,06 cm²)

 

Asl = 30.69 cm².

 

vRdi

 

 

Shear verification under seismical situations

 

Design shear resistance (EC8)

 

Verification:

Verification

 

RC Wall Designer results

 

Results

Verification is passed.

 

The wall is designed as a plain concrete wall.

 

 

VRd,max calculation

 

VRd,max calculation

 

 

Notes

 

Shear at the interface between concrete cast at different times (EC8)

 

Shear at the interface between concrete cast at different times (EC8)

 

Shear resistance at interface

 

 

 

 

 

 

 

 

 

 