The Design Assumptions tab, from Assumption panel, contains commands for defining general, design, seismic, buckling, and reinforced concrete assumptions as well as hypothesis related to concrete covers.
Note: The command’s dialog box content changes depending on the chosen standard.
- The General Design dialog allows you to define general hypotheses used in wall/wall group design which are based on ACI, CSA or Eurocode 2 and the National Annex, depending on the country selected in Localisation dialog.

The General Design dialog box
The General Design tab lets you define the stress-strain diagram, the creep parameters as well as the safety factors for concrete and steel materials:
Reinforcement stress-strain curve
Allows the selection of the stress-strain law:
- Horizontal top branch: diagram for the design of sections with a horizontal top branch without the need to check the strain limit, according to chapter 3.2.7 (2) from EN 1992-1-1.
- Inclined top branch: diagram for the design of sections with an inclined top branch, with a strain limit of ɛud, , according to chapter 3.2.7 (2) from EN 1992-1-1; if this option is checked, a value can be entered for k.
Note: k is the ratio of tensile strength to the yield stress. According to chapter 3.2.4 from EN 1992-1-1, k = (ft/fy)k .
Creep
Creep is a time-dependent property of concrete; its effects should be generally taken into account for the verification of serviceability limit states (see chapter 2.3.2.2 from EN 1992-1-1).
- Creep coefficient: select φ (∞, t0) as the final creep coefficient, according to EN 1992-1-1, chapter 3.1.4 or φ (t, t0) as the creep coefficient on a specified period, according to EN 1992-1-1, chapter 5.10.6(2)
- Relative Humidity (RH): enter a value for the ambient relative humidity, RH percentage. The default value is 50%.
- Concrete loading age: enter the age of concrete at first loading, t0, in days. The default value is 28 days.
- Concrete age (t): when the creep φ (t, t0) option is enabled, defines the age of the concrete at the considered instant moment, in days. The default is 365 days.
- Concrete shrinkage age (ts): enter a value for ts , the age of concrete at the beginning of the drying, in days. The default is 2 days.
- Cement class: select R (rapid), N (normal), or L (slow), defined according to EN 1992-1-1, chapter 3.1.2 (6).
Safety factors
Enter values for the partial factors for materials for ultimate limit states (see EN-1992-1-1, chapter 2.4.2.4). The values for safety factors may be different depending on the country chosen in Localisation, according to recommendations in the National Annex.
- γc = partial safety factor for concrete
According to chapter 2.4.2.4 (1), Table 2.1N from EN-1992-1-1:
- the default value is 1.5 for ULS situations
- the default value is 1.2 for ULS-accidental situations
According to chapter 5.2.4.(3), NOTE 2 from EN-1998-1:
- the default value is 1.3 for ULS-seismic situations
- γs = partial safety factor for reinforcing steel
According to chapter 2.4.2.4 (1), Table 2.1N from EN-1992-1-1:
- the default value is 1.15 for ULS situations
- the default value is 1.0 for ULS-accidental situations
According to chapter 5.2.4.(3), NOTE 2 from EN-1998-1:
- the default value is 1.0 for ULS-seismic situations
- The Wall design allows you to define the main assumptions used in the automatic design process, which are based on ACI, CSA or Eurocode 2 standards and the National Annex, depending on the country selected in Localisation dialog.

The Wall Design dialog box
General: allows you to select the load diffusion angle value (depends on wall type), the definitions of the load transversal eccentricity and the maximum width for the intervals in buckling verification:
- Reinforced wall load diffusion angle: impose the load diffusion angle for reinforced wall calculation. The default value is 33,7°.

Reinforced wall load diffusion angle
- Unreinforced wall load diffusion angle: impose the load diffusion angle for unreinforced wall calculation. The default value is 18,7°.

Unreinforced wall load diffusion angle
- Transversal eccentricity: impose the load transversal eccentricity.

- Buckling maximum interval width: impose the maximum width for the intervals in buckling verification. The default value is 500 mm.
Efforts calculation:
- Method
- Strips method: This method is the only method available when wall type is Wall.
Choose to calculate the wall using the strips calculation method according to French norm DTU 23.1. The wall is divided into several strips and each strip is individually analyzed.
Axial verification and reinforcement are computed using the average efforts on strips.
The method is not recommended for shear walls because only normal loads are considered in this method.
- Composed bending
When wall type is Shear Wall, the recommended method is Composed bending.
In this case, the longitudinal reinforcement is designed in composed bending, considering:
- a bw * lw concrete section (bw: wall thickness and lw: wall length)
- a (NEd,MEd) set of resulting forces (including the seismical forces from Newmark combinations) as well as the 2nd order effects if any.

This results in an Af reinforcement area, as stiffeners on each edge of the wall.

- Impose strip width
Strip width can be imposed by the user, otherwise, the maximum strip width is calculated according to 4.2.2.4 from DTU.
- Iteration precision for neutral axis position
This parameter allows for a more accurate determination of the neutral axis position. It imposes the increment step used in the iterative calculation of neutral axis position, used in Composed bending calculation method.
The 0,1 ‰ default ensures the calculation time will not be excessive.
Yet, at the end of the calculation, should the internal forces be too conservative compared to the design forces, the user can input a more accurate value (0,01 ‰) allowing for a more precise determination of the neutral axis, despite a longer calculation time.
Vertical reinforcement
- Method automatic detection
When enabled the used method will automatically be detected according to the applied loads.
- Method
When the chosen wall type is Shear wall, several methods are available to design the vertical reinforcement:

- Simplified (FD P18-717): available only when the concrete annex code is France, if the element is subjected only to axial loads.
- Method based on Nominal curvature (§5.8.8 from EN1992-1-1).
- Nominal stiffness (§5.8.7 from EN1992-1-1)
- General method (§5.8.6 from EN1992-1-1).
Note: This section is not available when wall type is Wall.
- Reinforcement precision
The parameter imposes the increment step used in the iterative calculation of reinforcement bars.
Horizontal reinforcement
- Strut slope
The angle between concrete compression struts and the main tension chord, according to 6.2.3 from EN 1992-1-1.
- The Seismic design command opens a dialog box where you can define seismic analysis parameters specific for the geographical area where the building is located and when the Seismic Dispositions box is checked. Hypotheses defined in this dialog are based on ACI, CSA, or Eurocode 2 and the National Annex, depending on the country selected in Localisation dialog.
The Seismic Design dialog box content changes depending on the chosen standard and the parameters are used for the shear force verification.

Note: Seismic Design dialog is available only if the wall type is Shear Wall.
- The Seismic characteristics dialog box contain the parameters related to the special provisions.
Note: Seismic characteristics dialog is available only if the wall type is Shear Wall and when the Seismic Dispositions box from Seismic Design dialog is checked.

The Seismic characteristics dialog box
Wall seismic characteristics
- Element type: choose from Large wall (5.4.2.5 from EN1998-1) or Ductile wall (5.4.2.4 from EN1998-1).
- Ductility: choose the ductility class (dissipative structural behavior) from the drop-down list: DCL (Low ductility, only available for Large wall), DCM (Medium ductility), and DCH (High ductility, only available for Ductile wall).
- Zone type: influence on the ρ value used in the EC8 shear checks (for the shear at the interface verification). The calculation of the reinforcement percentage, ρ, to take into account is different according to the position of the wall:
- Critical - the calculation of the reinforcement percentage is carried out considering only the vertical bars, Ar, distributed on a length (lw - 2 * lc, lc being the confined length of the edge stiffeners.
- Current - the calculation of the reinforcement percentage is carried out considering the distributed vertical reinforcement, Ar, plus the reinforcements of the edge stiffener, Ac, which is in the compressed zone: either a section (Ar + Ac) over a length (lw - lc).
Ductile walls parameters
Available only when Ductile wall is selected from the Element type command.

- T1: defines fundamental period of vibration. The default parameter is 0.25 seconds.
- YRD: defines model partial factor, according to Table F.2, Annex F from EN 1998-5. The default parameter is 1.2.
- Reinforcement for diagonal tension failure: provides additional reinforcement for wall web according to 5.5.3.4.3 from EN 1998-1.
- Additional stiffeners: allows you to add intermediate stiffeners along the wall length.

- The Reinforced Concrete command opens a dialog box where you can define the properties of the materials, both Concrete and Steel.
Hypotheses defined in this dialog are based on ACI, CSA, or Eurocode 2 and the National Annex, depending on the country selected in Localisation dialog.

The Reinforced Concrete dialog box
Concrete
- Class: allows the selection of the desired concrete class from the combo-box (the class can also be user-defined).
- fck: characteristic compressive strength of concrete, according to chapter 3.1.2 from EN 1992-1-1.
- ρ: density of concrete.
- Aggregate size: defines the maximum size of the aggregate used to calculate the clear distance (horizontal and vertical) between individual parallel bars or horizontal layers of parallel bars, in accordance to 8.2.(2) from EN1992-1-1.
Steel
- fyk: characteristic yield strength of reinforcement, according to Annex C from EN 1992-1-1.
- fywk: yield strength of reinforcement.
- Ductility class: allows you to select the steel ductility class (Class A, Class B, or Class C) and corresponding strain at maximum force, according to Annex C from EN 1992-1-1.
- Limit tensile stress in transverse reinforcement: this option limits the transversal reinforcement stresses to 0.8 * fywk
- The Interface verification command allows you to define the parameters used to verify the interface between concrete cast at different times.

The Interface verification dialog box
Exposure class: the exposure class related to environmental conditions in accordance with EN 206-1 (see Table 4.1 from EN 1992-1-1:2004)
Interface roughness: determines c and µ factors depends on the interface roughness according to 6.2.5 (2) from EN 1992-1-1: Very smooth, Smooth, Rough, Indented.
Interface position: defines the interface position at Top, Middle, Bottom, or an Imposed height.
Imposed interface height: defines the interface height.
Interface reinforcement: allows you to select this option to provide additional reinforcement across the interface.
- The Buckling Assumptions dialog allows you to define the wall support conditions and the buckling length coefficients. Assumptions defined in this dialog are based on ACI, CSA, or Eurocode 2 and the National Annex, depending on the country selected in Localisation dialog.
The dialog box content changes depending on the chosen standard, as seen below.

The Buckling Assumptions dialog box
There are two situations:
1. The wall has no links with other walls (not stiffened laterally). For this situation, in Supports conditions drop-down list only the options No continuity with floor at edges, Continuity with floor at one edge, Continuity with floor at both edges are active and Free at one edge, Fixed at two edges, Fixed at three edges, and Fixed at four edges are grayed.

No continuity with floor at edges

Continuity with floor at one edge

Continuity with floor at both edges

2. The wall has another perpendicular wall at least at one of its lateral edges (laterally stiffened). For this second situation, in Supports conditions drop-down list the options No continuity with floor at edges, Continuity with floor at one edge, Continuity with floor at both edges are grayed and Free at one edge, Fixed at two edges, Fixed at three edges, Fixed at four edges are active.

Note: If the wall has another perpendicular wall at least at one of its lateral edges and if the wall configuration corresponds to one of the cases below, then the option is automatically set. If not, the user should choose by themselves one of the 4 active options.
Fixed at three edges

Fixed at four edges

Note: The program also automatically chooses the suitable option as follows: for any cases which are not found among all the ones mentioned above, the first option from the active set of options (depending on the 2 detailed situations) will be set as default.
Reinforced wall buckling coefficient: buckling length coefficient for reinforced wall case
Unreinforced wall buckling coefficient: buckling length coefficient for unreinforced wall case
- The Concrete Covers command opens a dialog box where you can define wall concrete cover and parameters further used to perform a minimum cover verification (comparison between the defined concrete cover value and the minimum concrete cover calculated according to the norms). The dialog box content changes depending on the chosen standard selected in Localisation dialog.

The Concrete Covers dialog box
Concrete cover: define the reinforcement concrete cover of the current wall.
Minimum concrete cover verification: check this option to automatically update the concrete cover value, according to chapter 4.4.1.2 from EN 1992-1-1:
- The nominal cover […] is defined as a minimum cover, cmin (see 4.4.1.2), plus an allowance in design for deviation, ∆Cdev (see 4.4.1.3): cnom = cmin + ∆Cdev.
- The value of ∆Cdev […] the recommended value is 10 mm (4.4.1.3.(2) from EN1992-1-1).
- The greater value for cmin satisfying the requirements for both bond and environmental conditions shall be used: cmin = max {{cmin,b; cmin,dur + ∆Cdur,γ - ∆Cdur,st - ∆Cdur,add; 10 mm}}.
Notes:
1. The concrete cover may be increased by the additive safety element ΔCdur,γ […].
2. The recommended value is 0 mm (4.4.1.2(6) from EN1992-1-1).
3. Where stainless steel is used or where other special measures have been taken, the minimum cover may be reduced by ΔCdur,st. For such situations, the effects on all relevant material properties should be considered, including bond. The recommended value, without further specification, is 0 mm (4.4.1.2(7) from EN1992-1-1).
4. For concrete with additional protection (e.g. coating) the minimum cover may be reduced by ΔCdur,add.
5. The recommended value, without further specification, is 0 mm based on chapter 4.4.1.2(8) from EN1992-1-1.
ΔCdev: allowance in design for deviation, according to chapter 4.4.1.3 from EN 1992-1-1.
ΔCdur,γ: additive safety element, according to chapter 4.4.1.2 (7) from EN 1992-1-1.
ΔCdur,st: reduction of the minimum Concrete cover value for use of stainless steel, according to chapter 4.4.1.2 (7) from EN 1992-1-1.
ΔCdur,add: reduction of the minimum Concrete cover value for use of additional protection, according to chapter 4.4.1.2 (8) from EN 1992-1-1.
Structural class: select the structural class from the drop-down (S1 - S6) (see chapter 4.4.1.2 (5) from EN 1992-1-1).
Reduce structural class: reduction of the current structural class according to Table 4.3N from EN1992-1-1.
Final structural class: displays the final eventually reduced structural class which will be further used in design.